Breaking Capacity | Material | Operating Temperature |
35A at 5000V AC (500mA-950mA) | Fuse Case--Plastic Element--Alloy Lead--Highvoltage Wire | -40℃~+125℃ |
Testing current | Blow Time | |
Min | Max | |
115% | 4 hours | - |
210% | - | 20s |
275% | 20ms | 150ms |
400% | 8ms | 400ms |
1000% | - | 80ms |
● Pending
○ Approvals
Current Rating | Voltage Rating | Norminal Melting I²T(A²sec) For Reference | Approvals | ||||
500mA | 5000V | 0.123 | ● | ○ | ○ | ○ | ○ |
550mA | 5000V | 0.161 | ● | ○ | ○ | ○ | ○ |
600mA | 5000V | 0.261 | ● | ○ | ○ | ○ | ○ |
650mA | 5000V | 0.343 | ● | ○ | ○ | ○ | ○ |
700mA | 5000V | 0.416 | ● | ○ | ○ | ○ | ○ |
750mA | 5000V | 0.567 | ● | ○ | ○ | ○ | ○ |
800mA | 5000V | 0.802 | ● | ○ | ○ | ○ | ○ |
850mA | 5000V | 1.196 | ● | ○ | ○ | ○ | ○ |
900mA | 5000V | 1.685 | ● | ○ | ○ | ○ | ○ |
950mA | 5000V | 2.331 | ● | ○ | ○ | ○ | ○ |